Quick answer: The design of an operation theatre starts outside the room, with four zones: outer, clean, sterile and disposal. Patients, staff, sterile supplies and waste then each follow a one-way route through them. Air pressure also follows the same order, highest in the theatre and lowest at disposal. Get the zones right, and the rest of the design of an operation theatre follows.

A perfect theatre in the wrong place still fails. For instance, a scrub bay across the corridor undoes the air system every hour. So this guide covers the design of an operation theatre as a suite: zones, flows and the rooms that must touch.

The four zones in the design of an operation theatre

Reception, the patient transfer bay, staff changing rooms and the lounge form the outer or protective zone. The clean zone then holds the anaesthetic room, the scrub bay, the sterile store entry and the recovery area. The sterile zone is the theatre itself, together with its lay-up space. Finally, the disposal zone holds the dirty utility and the disposal corridor. The international Health Facility Guidelines, which DHA follows, describe the same four layers.

Design of operation theatre zones: outer, clean, sterile and disposal zones in a UAE surgical suite

Four one-way flows

Each zone exists to keep four flows apart. Patients move from the transfer bay to the anaesthetic room, into the theatre and out to recovery. Staff change, then walk a clean corridor to the scrub bay and into the theatre. Similarly, sterile supplies travel from CSSD to the sterile store and through a pass box into the theatre. Waste leaves the theatre into the dirty utility and then along the disposal corridor, never back through the clean side. In a good suite, no two flows share a door.

Design of operation theatre workflow: patient, staff, sterile supply and waste routes kept apart

Rooms that must touch the theatre

Adjacency decides whether the flows work. The scrub bay sits directly outside the staff door, so a scrubbed surgeon takes three steps, not thirty. Where used, the anaesthetic room also shares a wall and a door with the theatre. The sterile store opens into the theatre through a pass box. The dirty utility sits off the opposite side with its own exit. Recovery should be within 30 m, because anaesthetists move between both. The theatre itself follows our modular operation theatre design guide.

Adjacency diagram: scrub bay, anaesthetic room, sterile store, dirty utility and recovery around the sterile zone

Sizes and door counts

Allow 15 to 18 m² for the anaesthetic room and 6 to 8 m² for a two or three bay scrub. The sterile store needs 10 to 12 m² and the dirty utility 8 to 10 m². Recovery also needs about 1.5 bays per theatre at 9 to 12 m² each. Then count the doors. A theatre needs two, or three at most: patient, staff and supply. Every extra door costs pressure, so the design of an operation theatre removes doors rather than adding them. Our guide to equipment for an operation theatre then covers what goes inside.

Design of operation theatre sizes: anaesthetic room, scrub bay, sterile store, dirty utility and recovery with door counts

Pressure in the design of an operation theatre follows the zones

The theatre sits at about 10 Pa above the corridor, the sterile store and scrub bay at about 5 Pa. The clean corridor sits near neutral and the dirty utility negative. Air therefore always moves from sterile to dirty, in the same direction as the waste. In the UAE, moreover, this cascade is part of the licensing file, as our guide to hospital operation theatre design standards explains. An isolation room in the same suite needs its own negative cascade, so place it at the disposal end.

Suite pressure cascade: 10 Pa at the top, scrub and store 5 Pa, corridor neutral, dirty utility negative

Frequently asked questions

What are the zones in the design of an operation theatre?
Four: outer for reception and changing, clean for anaesthesia and scrub, sterile for the theatre, disposal for waste.

Why does the scrub bay sit outside the theatre door?
So a scrubbed surgeon enters directly without crossing a corridor, which protects the gown and the theatre air.

How many doors should a theatre have?
Two, or three at most: patient, staff and supply. Each extra door, however, leaks pressure and crosses a flow.

Does the design of an operation theatre need an anaesthetic room?
UK-style suites use one; FGI-style suites induce in the theatre. DHA accepts both, so the operator decides.

Where does an isolation room go?
At the disposal end of the suite, with its own negative-pressure cascade and ante-room, away from the sterile zone.

Reviewing the design of an operation theatre suite?

Send us your floor plan. We then return a zoned layout, the flow diagram and an itemised AED quote within two working days. WhatsApp +91 93232 98094 or request a free consultation at agoraccs.com/contact.